Head pressure control valve operation ori/ord – ClimaCool IOM AR2 SERIES User Manual

Page 58

Advertising
background image

56

www.climacoolcorp.com

®

REFRIGERANT CHARGING PROCEDURES — Normally

this information is supplied by the equipment manufacturer . And

when it is available, it should be followed . When it is not available

from the equipment manufacturer, the following suggestions are

recommended . Once the amount of extra refrigerant charge is

calculated, care must be taken in charging the system to insure the

proper total amount of refrigerant getting into the system . This is

especially true if the ambient temperature is below 70°F and the

liquid drain valve (ORI) is throttling the refrigerant flow from the

condenser . A step by step procedure is given below for the two

possible situations that can exist . And depending on the ambient

temperature at the time the system is charged, each should be

carefully followed to insure proper system operation in both summer

and winter . In either case, a liquid seal must be established in the

receiver before the system can start to function correctly .

NOTE: While charging any system with head pressure control, the

outdoor ambient temperature must be known . And if the system has

compressor unloaders, it is important to know if they are functioning

during the charging procedure . To keep this procedure as simple

as possible, it is recommended that the unloaders be locked out

(compressor fully loaded) during charging .

Charging of Systems with Sporlan Head Pressure Control in

Ambients ABOVE 70°F (After normal evacuation procedures)

BEFORE STARTING SYSTEM

1 . Connect refrigerant cylinder to a charging or gauge port on the

receiver outlet valve .

2 . Open the receiver valve approximately one-half way (so receiver

and liquid line are connected to charging or gauge port) .

3 . Charge liquid refrigerant into the high side of the system .

Weighing the charge is recommended with the initial charge

consisting of approximately 2 .5 pounds per system ton .

4 . Remove the refrigerant drum and connect it to the suction side of

the compressor .

5 . Charge refrigerant vapor into the low side until the pressure is

above atmospheric pressure . Do not admit liquid refrigerant into

the low side .

6 . Start the system .

7 . Observe sight glass (at receiver outlet) to see if system is properly

charged for normal refrigeration cycle . CAUTION: Bubbles in the

sight glass can be caused by flashing due to pressure drop from

pipe or accessory losses, etc .

8 . If the sight glass shows bubbles, more refrigerant should be

added, while allowing sufficient time for the refrigerant to

stabilize and clear the sight glass .

9 . The extra refrigerant charge for head pressure control should be

weighed in now by admitting liquid refrigerant to the high side .

Charging of Systems with Sporlan Head Pressure Control in

Ambients BELOW 70°F (After normal evacuation procedures)

NOTE: When charging in ambients below 70°F the procedure is very

critical . Be sure to adhere to the following steps without fail . Failure

to do so will result in overcharging the system .

1 . Follow instructions 1 through 7 above .

2 . If the ORI valve setting is correct for the system being charged,

it is quite likely that some refrigerant will be backed up into the

condenser and the sight glass will indicate bubbles in the liquid

line .

3 . Add more refrigerant, while allowing sufficient time for the

refrigerant to stabilize and clear the sight glass .

4 . At this point the system is correctly charged for this type of head

pressure control at the ambient temperature that exists while the

charging procedure is taking place .

5 . If the system is designed to operate at ambients below the ambient

that exists during charging, additional charge will have to be

added now .

6 . To calculate the additional charge required, follow the examples

outlined under “Refrigerant Charge” except remember that the

“head pressure control charge” is partially charged already . Refer

to Tables 2 and 3 .

The difference in percentages between the minimum design ambient

temperature and the ambient temperature at the time the system is

charged gives the percent of extra charge still needed in the system .

E .g ., if this system was charged at an ambient of 50°F, we have

approximately 40% of the extra charge in the system . This holds

true as long as the compressor unloaders were not operating during

charging . Therefore, the additional charge required is 95 minus 40 or

55% of the total extra charge calculated previously . This is .55 x 119

or 65 pounds . Since good system performance during low ambient

operation depends on proper refrigerant charge, it is very important

that this phase of the installation procedure be done carefully . Many

times, poor system performance will be due to too little or too much

charge . And in many cases this will be the last item suspected .

Head Pressure Control Valve Operation ORI/ORD

Advertising