Hot gas bypass line – AAON CB-060 User Manual

Page 17

Advertising
background image

17

A double suction riser can be applied to the
situation of part load operation with a
suction riser. A double suction riser is
designed to return oil at minimum load
while not incurring excessive frictional
losses at full load. A double suction riser
consists of a small diameter riser in parallel
with a larger diameter riser, and a trap at the
base of the large riser. At minimum
capacity, refrigerant velocity is not sufficient
to carry oil up both risers, and it collects in
the trap, effectively closing off the larger
diameter riser, and diverting refrigerant up
the small riser where velocity of the
refrigerant is sufficient to maintain oil flow.
At full load, the mass flow clears the trap of
oil, and refrigerant is carried through both
risers. The smaller diameter pipe should be
sized to return oil at minimum load, while
the larger diameter pipe should be sized so
that flow through both pipes provides
acceptable pressure drop at full load.

Suction Line Insulation
The entire suction line should be insulated
with a minimum 1 inch thick Armaflex
insulation. This prevents condensation from
forming on the line, and reduces any
potential loss in capacity associated with
heat gain placing additional load on the
system.

Suction Line Guidelines
For proper performance, suction line
velocities less than a 4,000 fpm maximum
are recommended. The minimum velocity
required to return oil is dependent on the
pipe diameter, however, a general guideline
of 1,000 fpm minimum may be applied.

In a fashion similar to the liquid line, a
common guideline to consider is a system
design with pressure losses due to friction
through the

line

not

to exceed a

corresponding 1-2°F change in saturation
temperature.

At points where small pipe size can be used
to provide sufficient velocity to return oil in
vertical risers at part loads, greater pressure
losses are incurred at full loads. This can be
compensated for by over sizing the
horizontal runs and vertical drop sections.
This will however require additional
refrigerant charge.

Circuits with variable capacity scroll
compressors require suction riser traps every
10 feet.

Suction Line Accessories
If the job requirements specify suction
accumulators, they must be separately
purchased and field installed.

Hot Gas Bypass Line
Hot Gas Bypass (HGB) is available for use
with DX systems that may experience low
suction pressure during the operating cycle.
This may be due to varying load conditions
associated with VAV applications or units
supplying a large percentage of outside air.
The system is designed to divert refrigerant
from the compressor discharge to the low
pressure side of the system in order to keep
the evaporator from freezing and to maintain
adequate refrigerant velocity for oil return at
minimum load.

Hot discharge gas is redirected to the
evaporator inlet via an auxiliary side
connector (ASC) to false load the evaporator
when reduced suction pressure is sensed.
Field piping between the condensing unit
and the evaporator is required.

Hot Gas Bypass Piping Considerations for
Evaporator above Condensing Unit
Pitch the hot gas bypass line downward in
the direction of refrigerant flow, toward the
evaporator.