Caution – AAON CB-060 User Manual

Page 20

Advertising
background image

20

Table 2 - Predetermined Line sizes for CB units with two step compressors and R-410A

Model

Connection Sizes

Predetermined Line Size

Liquid

Suction

Hot Gas

Liquid

Suction

HGBP*

HGRH**

CB-024

3/8”

3/4”

3/8”

3/8”

3/4”

3/8”

3/8”

CB-036

3/8”

3/4”

3/8”

3/8”

3/4”

3/8”

1/2”

CB-048

3/8”

7/8”

1/2”

1/2”

7/8”

1/2”

1/2”

CB-060

3/8”

7/8”

1/2”

1/2”

7/8”

1/2”

1/2”

* Hot Gas Bypass line
** Hot Gas Reheat line

Figure 2 - Riser height versus total equivalent line length


Note: Figure 2 is for R-410A split system applications with two step compressor CB-024
through CB-060 units. The region of acceptable riser height is the lighter area. Select the
corresponding predetermined line size from Table 2 above.











Total Equivalent Line Length in this
figure is limited to 160 equivalent
feet.