AAON CB-060 User Manual

Page 27

Advertising
background image

27

Figure 4 - Compressor Controller Flash Code Details

Table 7 - Thermistor Temperature vs. Resistance Values

°C

°F

°C

°F

-40

-40

2889.60

75

167

12.73

-35

-31

2087.22

80

176

10.79

-30

-22

1522.20

85

185

9.20

-25

-13

1121.44

90

194

7.87

-20

-4

834.72

95

203

6.77

-15

5

627.28

100

212

5.85

-10

14

475.74

105

221

5.09

-5

23

363.99

110

230

4.45

0

32

280.82

115

239

3.87

5

41

218.41

120

248

3.35

10

50

171.17

125

257

2.92

15

59

135.14

130

266

2.58

20

68

107.44

135

275

2.28

25

77

86.00

140

284

2.02

30

86

69.28

145

293

1.80

35

95

56.16

150

302

1.59

40

104

45.81

155

311

1.39

45

113

37.58

160

320

1.25

50

122

30.99

165

329

1.12

55

131

25.68

170

338

1.01

60

140

21.40

175

347

0.92

65

149

17.91

180

356

0.83

70

158

15.07

Advertising