Correct an overcharged system by reducing
the amount of refrigerant in the system to
lower the sub-cooling.










The system is undercharged if the superheat
is too high and the sub-cooling is too low

Correct an undercharged system by adding
refrigerant to the system to reduce superheat
and raise sub-cooling.

If the sub-cooling is correct and the
superheat is too high, the TXV may need
adjustment to correct the superheat.










Air Flow

Table 4 - Performance Testing Air Flow Setpoints

Model

Cooling Stage 2

(cfm)

Cooling Stage 1

(cfm)

Heating Stage 2

(cfm)

Heating Stage 1

(cfm)

CB-B-024-*-*-1

885

663.75

885

796.5

CB-B-036-*-*-1

1250

937.5

1250

1125

CB-B-048-*-*-1

1500

1125

1500

1350

CB-B-060-*-*-1

1545

1158.75

1545

1390.5



DO NOT OVERCHARGE!


Refrigerant overcharging leads to
excess refrigerant in the condenser
coils resulting in elevated compressor
discharge pressure.

CAUTION


Before

completing

startup

and

leaving the unit a complete operating
cycle should be observed to verify
that all components are functioning
properly.