8 Alarm messages

Message

Probable causes

Solution

24V SHORT-CIRC.

Short circuit 24 V

Reset the boiler . Contact your fitter.

Faults

Probable causes

Solution

BURNER FAILURE

Igniter fault
Ionization error
Gas valve defective
No gas or presence of air in the pipe

Reset the boiler . Contact your fitter.

I-CURRENT FAIL

Ionization fault during operation

MCBA FAILURE XX

Internal safety control box fault

MCBA FAILURE 5

External influences

MCBA FAILURE 11

Internal fault

DEF.MCBA 24

Boiler reversal sensor and return sensor

VALVE FAIL

Combined gas valve unit defective

REARM CVI

Control error

MCBA.COM.FAULT

Communication error between DIEMATIC and
safety control box

ROOM S.A FAIL.
ROOM S.B FAIL.
ROOM S.C FAIL.
OUTL S.B FAIL.
OUTL S.C FAIL.
OUTSI. S.FAIL.
SWIM.P. S.FAIL

Fault in the corresponding sensor

FAN OFF FAIL

The fan is not working

FAN ON FAIL

The fan is working constantly

BOILER S.FAIL.

Boiler sensor defective

DHW S. FAILURE

Domestic hot water sensor defective

SMOKE S. FAIL.

Draught diverter thermostat defective

BACK S.FAILURE

Return sensor defective

PARASIT FLAME

Detection of a parasite flame

STB BOILER

Outlet temperature > 97°C

STB SMOKE

Flue gas temperature > 105 °C

STB BACK

Return temperature too high