Turning on the antifreeze function, 5 turning on the antifreeze function – DE DIETRICH VIVADENS MCR 24, MCR .._.. MI User Manual

Page 19

Advertising
background image

4.5

Turning on the antifreeze function

We recommend setting the boiler thermostat to a value off 10°C if

using a classic installation.
Define parameter p4 as 1 (energy-saving mode), the heat

retention function will be deactivated.
Installation and room antifreeze protection is guaranteed if you are

absent.
If the temperature of the central heating water in the boiler falls too

much, the integrated protection device switches itself on:

4

If the water temperature is lower than 7°C, the circulating pump is

activated.

4

If the water temperature is lower than 3°C, the boiler is activated.

4

When the water temperature is above 10 °C, the boiler is switched

off and the circulation pump runs for another 15 minutes.

CAUTION

This function is a protection device for the boiler only, not

for the system or buiding fabric.

CAUTION

If a room thermostat, connected via connectors 7 and 8,

is activated, the boiler will operate permanently until it

reaches the flow setting point.

MCR 24 MCR 24/28 MI MCR 30/35 MI MCR 34/39 MI

4. Operating the appliance

160513 - 300015874-001-01

18

Advertising