Troubleshooting, Anti-hunting, Messages (code type bxx or mxx) – DE DIETRICH INNOVENS MCA 35 User Manual

Page 32: 6 troubleshooting, 1 anti-hunting, 2 messages (code type bxx or mxx)

Advertising
background image

6 Troubleshooting

6.1

Anti-hunting

When the boiler is in Anti-short-cycle operating mode, the symbol ?

flashes.
1. Press the "?" key.

The message Operation assured when the restart temperature
will be reached

is displayed. When the restart temperature is

reached, operation will be guaranteed.

This message is not an error message but an item of

information.

6.2

Messages (Code type Bxx or Mxx)

In the case of failure, the control panel displays a message and a

corresponding code.
1. Make a note of the code displayed.

The code is important for the correct and rapid diagnosis of the

type of failure and for any technical assistance that may be

needed.

2. Switch the boiler off and switch back on.

The boiler starts up again automatically when the reason for the

blocking has been removed.

3. If the code is displayed again, correct the problem by following the

instructions in the table below:

Code Messages

Description

Checking / solution

B00

BL.PSU ERROR

The PSU PCB is incorrectly

configured

Parameter error on the PSU PCB

4

Contact the professional who takes care of maintenance of

the appliance

B01

BL.MAX BOILER

Maximum flow temperature

exceeded

The water flow in the installation is insufficient

4

Check the circulation (direction, pump, valves)

B02

BL.HEATING
SPEED

The increase in flow temperature

has exceeded its maximum limit

The water flow in the installation is insufficient

4

Check the circulation (direction, pump, valves)

4

Check the water pressure

Sensor error

4

Contact the professional who takes care of maintenance of

the appliance

B07

BL.DT OUTL RET.

Maximum difference between the

flow and return temperature

exceeded

The water flow in the installation is insufficient

4

Check the circulation (direction, pump, valves)

4

Check the water pressure

Sensor error

4

Contact the professional who takes care of maintenance of

the appliance

6. Troubleshooting

MCA 35

31

24/08/2011 - 300024162-001-B

Advertising