Technical specifications, 7 technical specifications, 1 technical specifications – DE DIETRICH INNOVENS MCA 35 User Manual

Page 40

Advertising
background image

7 Technical specifications

7.1

Technical specifications

Boiler type

MCA 35

General
Flow rate setting

Adjustable

Modulating, Start/Stop, 0 - 10 V

Nominal output (Pn)

Heating System (80/60 °C)

minimum-maximum kW

6,3 - 33,7

Factory setting

kW

33,7

Data on the gases and combustion gases
Gas consumption - Natural gas H (G20) minimum-maximum m

3

/h

0,69 - 3,71

Gas consumption - Propane G31

minimum-maximum m

3

/h

0,27 - 1,44

NOx-Emission per year (n =1)

mg/kWh 42

Characteristics of the heating circuit
Water content

l

2,3

Water temperature

maximum

°C

110

Operating temperature

maximum

°C

90

Electrical characteristics
Power supply voltage

VAC

230

Power consumption - Full load

maximum

W

173

Factory setting

W

151

Electrical protection index

IPX4D

Other characteristics
Total weight (empty)

kg

39

Acoustic level at 1 metre at high speed

dB(A)

45

7. Technical specifications

MCA 35

39

24/08/2011 - 300024162-001-B