Technical specifications, 7 technical specifications, 1 technical specifications – DE DIETRICH INNOVENS MCA 35 User Manual
Page 40
7 Technical specifications
7.1
Technical specifications
Boiler type
MCA 35
General
Flow rate setting
Adjustable
Modulating, Start/Stop, 0 - 10 V
Nominal output (Pn)
Heating System (80/60 °C)
minimum-maximum kW
6,3 - 33,7
Factory setting
kW
33,7
Data on the gases and combustion gases
Gas consumption - Natural gas H (G20) minimum-maximum m
3
/h
0,69 - 3,71
Gas consumption - Propane G31
minimum-maximum m
3
/h
0,27 - 1,44
NOx-Emission per year (n =1)
mg/kWh 42
Characteristics of the heating circuit
Water content
l
2,3
Water temperature
maximum
°C
110
Operating temperature
maximum
°C
90
Electrical characteristics
Power supply voltage
VAC
230
Power consumption - Full load
maximum
W
173
Factory setting
W
151
Electrical protection index
IPX4D
Other characteristics
Total weight (empty)
kg
39
Acoustic level at 1 metre at high speed
dB(A)
45
7. Technical specifications
MCA 35
39
24/08/2011 - 300024162-001-B