Code Faults

Cause
of the
fault

Description

Checking / solution

D03
D04

OUTL S.B FAIL.
OUTL S.C FAIL.

SCU

Circuit B flow sensor fault

Circuit C flow sensor fault
Remarks:

The circuit pump is running.

The 3-way valve motor on the circuit

is no longer powered and can be

adjusted manually.

Bad connection

Sensor fault

4

Contact the professional who takes care of

maintenance of the appliance

D05

OUTSI.S.FAIL.

SCU

Outside temperature sensor fault
Remarks:

The boiler operates on BOILER
MAX

temperature.

The valve setting is no longer

ensured but monitoring the

maximum temperature of the circuit

after the valve is ensured.

Valves may be manually operated.

Reheating the domestic hot water

remains ensured.

Bad connection

Sensor fault

4

Contact the professional who takes care of

maintenance of the appliance

D07

AUX.SENS.FAIL.

SCU

Auxiliary sensor fault

Bad connection

Sensor fault

4

Contact the professional who takes care of

maintenance of the appliance

D09

DHW S.FAILURE

SCU

Domestic hot water sensor fault
Remarks:

Heating of domestic hot water is no

longer ensured.

The load pump operates.

The load temperature of the dhw

tank is the same as the boiler.

Bad connection

Sensor fault

4

Contact the professional who takes care of

maintenance of the appliance

D11
D12
D13

ROOM S.A FAIL.
ROOM S.B FAIL.
ROOM S.C FAIL.

SCU

A room temperature sensor fault

B room temperature sensor fault

C room temperature sensor fault
Note:

The circuit concerned operates

without any influence from the room

sensor.

Bad connection

Sensor fault

4

Contact the professional who takes care of

maintenance of the appliance

D14

MC COM.FAIL

SCU

Communication failure between the

SCU PCB and the boiler radio

module

Bad connection

4

Check the link and the connectors

Boiler module failure

4

Change the boiler module

D15

ST.TANK S.FAIL

SCU

Storage tank sensor fault
Note:

The hot water storage tank

reheating operation is no longer

assured.

Bad connection

Sensor fault

4

Contact the professional who takes care of

maintenance of the appliance

D16
D16

SWIM.P.B. S.FAIL
SWIM.P.C. S.FAIL

SCU

Swimming pool sensor fault circuit

B

Swimming pool sensor fault circuit

C
Note:

Swimming pool reheating is always

done during the circuit's comfort

period.

Bad connection

Sensor fault

4

Contact the professional who takes care of

maintenance of the appliance

D17

DHW 2 S.FAIL

SCU

Sensor fault tank 2

Bad connection

Sensor fault

4

Contact the professional who takes care of

maintenance of the appliance

6. Troubleshooting