4 led message code, 5 measured values and adjustment parameters, Continuously green – DE DIETRICH DIETRISOL TRIO DT 250 - TRIO DT 350 User Manual

Page 12: Continuously red, Flashing green/red

Advertising
background image

12

TRIO DT 250 - TRIO DT 350

17/10/12 - 300028005-001-03

5.4 LED message code

„

Continuously green

At least one relay is closed.
Regulation operating normally (System Operating). Solar system
Operating. The temperature of the hot water tank (parameter TS)
increases.

„

Continuously red

All relays are open.
The installation is stopped. The solar collectors are not hot enough
(parameter TC) to enable operation.

„

Flashing green/red

- Initialisation phase

- Sensor fault.

See chapter Sensor fault.

- The installation is in manual mode.

For automatic operation, set parameter MM to 4.

- Maximum tank temperature exceeded.

The hot water tank has reached the set temperature and the
installation is in overheating safety mode or in cooling mode.

- Maximum temperature of the solar collectors exceeded.

The installation is in safety mode. It remains in this mode until the
temperature of the solar collectors has fallen back below the
maximum temperature.

5.5 Measured values and adjustment parameters



The regulator has a safety system that cuts off the tank at
temperatures of over 80°C.

Channel

Abbreviation

Range

Increment

Factory setting

Collector temperature

TC

[-50.0 ... 250.0] °C

-

-

Calorifier temperature

TS

[-50.0 ... 250.0] °C

-

-

Amount of heat

kWh

[0 ... 9999] kWh

-

-

Pump regime

PC

[0 ... 100] %

-

-

Self-calibration time

tc

[0 ... 5] minutes

-

-

Return temperature

TR

-50...250°C

-

-

Additional temperature

TM

-50...250°C

-

-

Type of installation

ANL

Installation 1
Installation 2

-

Installation 1

Temperature difference enabling the passage of the heating
return via the solar tank

DO

[0.5 ... 19.5] K

0.1

6

Temperature difference enabling heating return directly to the
boiler

DF

[0.4 ... 19.5] K

0.1

4

Reference temperature difference

DT

[10 ... 20] K

0.1

20

Zone changeover temperature (tank)

SZ

[20 ... 80] °C

0.1

55

Set temperature of the solar calorifier

SX

[20 ... 80] °C

0.1

60

Maximum collector temperature

CX

[100 ... 125] °C

0.1

100 °C

Self-calibration phase

tu

[1 ... 5] minutes

1

3

Pump minimum speed

PN

[50 ... 100] %

5

50

Tubular solar collector function

FT

[0 ... 1]

1

0

Maximum flow rate

Fx

[0 … 20] l/min

0.1

Installation 1: 6.7
Installation 2: 4.2

Manual mode

MM

[0 ... 4]

1

4

Software version

VN

-

-

1

Hardware version

PG

-

-

64.30

Measured values
Adjustment parameter

Advertising