APPENDIX 

Step Nine 

Controller Logic:  Please use the following guide to understand the operation of the controllers. 

1. Power LED:  Make sure the Green power LED is ON when power is supplied to the controller. 

2. Input LED:  For NC switch wiring, the input LED on the controller will be Amber when the switch reads no‐

flow and OFF when the switch reads flow. 

3. Invert Operation: When the input LED turn Off and On, the relay LED will also switch.  With invert Off, the 

relay LED will be On when the input LED is On and Off when the input LED is Off.  With invert On, the relay 
LED will be Off when the input LED is On and On when the input LED is Off

.

 

4. Relay Operation: The relay may be wired either NO or NC.  The normal state of the relay is when its LED is 

Off.  With the LED On, the relay is in the energized mode and all terminal connections are reversed. 

Troubleshooting: 

PROBLEM 

 

  SOLUTION 

Controller is powered, but nothing 
happens. 

First check the Power LED to make sure it is Green.  If not, check 
the  wiring,  power  and  make  sure  the  terminal  is  seated 
correctly over the 6‐pins.  

A  Flow  or  No‐Flow  condition  is 
met but the relay did not switch. 

Check  the  relay  by  switching  the  invert  switch.    Confirm  that 
relay click on and off as well as the relay LED.  

The  Flow  or  No‐Flow  is  not 
switching at the correct flow rate. 

The  flow  switch  may  need  to  be  adjusted.    Review  the  Flow 
Switch Calibration section on the previous page for instructions 
on  setting  the  actual  flow  switch.    Note:  access  to  the  flow 
switch  adjustment  is  difficult  and  requires  the  removal  of  the 
PCB assembly.  Use caution when performing this step. 

Trying  to  start  the  flow  but  the 
controller  keeps  turning  the  flow 
off. 

To restart a flow condition, the sensor needs to sense an actual 
flow  condition  before  changing  the  relay  in  the  controller.    A 
flow  switch  over‐ride  may  need  to  be  added  across  the  relay 
contacts  that  allows  for  a  true  flow  to  occur  before  switching 
back  to  the  controller.    The  use  of  a  moment  switch  is 
recommended for the over‐ride switch. 

Relay LED does not match my flow 
condition. 

The relay LED can be switched by either the reversing the wiring 
of the sensor to the controller or by flipping the invert switch.  
This  means  that  the  relay  LED  can  either  be  set  to  turn  on 
during  a  flow  condition  or  to  turn  off  during  a  no‐flow 
condition.    This  is  all  dependent  on  the  wiring  and  the  invert 
position. 

Relay  LED  does  not  match  the 
sensor’s LED indicator. 

The sensor’s LED will always be ON during a No‐Flow state and 
OFF during a Flow state, regardless of the switches wiring.  As 
per  above  the  input  LED  can  be  inverted  to  any  condition.    In 
some  applications,  they  will  match  and  in  others  they  will  be 
opposite.    This  is  all  dependent  on  the  application 
parameter/setup. 

 
 

 

 