Flowline LC30 Thermo-Flo User Manual

Page 7

Advertising
background image

Rev A 

LC900008 

7 of 14 

ELECTRICAL 

Step Five 

Connecting switches to input terminals:  Please note a difference between FLOWLINE flow switches.  All flow 
switches will be wired with the White wire to the (S) terminal.  Models FT10 ‐ _ _ _ 5 and GT10 ‐ _ _ _ 5 will be 
wired with the Green wire to the (‐) terminal).  The Red and Black wires can be wired to either the (+) terminal 
or (‐) terminal based upon switch polarity.  See the illustration below to indicate wiring for your switch.  Note: 
the Shield wire will be used only for long cable runs or where excessive electrical noise is present. 

Normally Closed 

Normally Open 

  
Switch Cable:  When installing a Flowline flow switch, 
adjust the cable away from the printed circuit boards 
in  the  controller  body.    Avoid  breaking  the  seal 
between  the  top  of  the  level  switch  and  the  plastic 
coated cable. 

 

VAC  Power  Input  Wiring:    Observe  the  labeling  on 
the LC30 Series.  Note: Polarity does not matter with 
the AC input terminal.
   

      

 

Relay Input Wiring:  The relay is a single pole, double 
throw type rated at 250 Volts AC, 16 Amps.  The two 
terminal  NO  and  NC  (normally  open  and  normally 
closed)  will  be  used  in  different  applications.  
Remember that the "normal" state is when the relay 
coil is de‐energized and the Red relay LED is Off / de‐
energized.   

 

 

 

Advertising