Flowline LC30 Thermo-Flo User Manual

Page 9

Advertising
background image

Rev A 

LC900008 

9 of 14 

INSTALLATION 

Step Six 

Mounting on a Sensor:  The following procedure should be used when mounting the controller directly on a 
flow sensor.  All power to the system must be off before installing the junction box.  

1. Prepare the sensor:  The following instructions assume the sensor is already mounted in a position on 

its fitting (as described in the sensor manual).  Note that because the insulation jacket of the sensor is 
less  flexible  than  most  (to  ensure  chemical  compatibility),  it  is  important  that  you  follow  the 
instructions exactly. 

a. Cut the wire 4‐1/4” from the top of the sensor. 
b. Using a 10 gauge wire stripper, strip the white outer layer of insulation from the last 1‐1/4” of 

the sensor wire.  Trim off and discard the exposed foil shield flush with the insulation jacket.  In 
long cable runs, do not cut off the drain wire. 

c. Using a 20 gauge wire stripper, strip the last ¼” of insulation from the signal wires. 

 

Important: Do not strip more than 0.2” (5mm) of insulation from any wire that will be connected to the 
terminal  strip.    Longer  insulated  wire  may  contact  the  terminal  strip  panel,  causing  a  short  circuit 
leading to a system failure.
  

2. Position the controller on the sensor:  To make the mounting and wiring easier, 

you must first remove the printer circuit board (PCB) from the controller. 

a. Unscrew the lid of the controller. 
b. Remove the two screws holding the PCB to the controller. 
c. Gently tip the controller to slide out the PCB and place it aside. 
d. Thread the pre‐trimmed sensor wires through the ¾” NPT entrance to the 

junction box, and place the controller in position over the sensor. 

e. Being careful not to cross the threads, screw the controller on the sensor.  

Stop when the cap of the sensor becomes flush with the bottom wall of the 
controller,  or  when  the  ½”  power  conduit  entrance  is  in  the  desired 
location. 

3. Connect the sensor input wires: 

a. Route the sensor‐wire so it stays as close to the housing as possible, but do 

not  bend  the  wire  sharply  at  the  cap  of  the  sensor.    (if  the  installation 
allows,  you  may  rotate  the  controller  and/or  the  sensor  until  the  wire 
outlet of the sensor is in the best position.) 

b. Position the PCB in the housing aligned with the two channels designed to 

hold it.  Do not insert the panel all the way into the housing, but let it rest 
on the top of the housing to facilitate the wiring. 

c. Using  a  small  screwdriver,  loosen  the  terminal  screws.    Insert  the  sensor 

wires into the hole on the sensor input terminal, and tighten the terminal 
screws. 

d. Once completed seat the PCB back into the channels and restore only one 

screw to hold the PCB in place. 

 

Advertising