Fitting the position feedback with stroke, Limiter to a pneumatic actuator size 50 to 80mm – Burkert Type 1062 User Manual

Page 19

Advertising
background image

19

Assembly

Type 1062

→

Fully tighten the duplication rod on
the actuator rod using a screwdriver
with a blade of suitable size.

→

Depressurize the actuator of a valve
which is normally closed (function
"A") or has a double effect (function
"I"): the valve recovers its default
position.

C
D

→

Insert the position feedback housing
into the duplication system "D"
setting the cable gland in the
direction desired and making sure,
on a mechanical contact version,
that you do not damage the contact
levers on the switches.

→

Fasten the housing and the dupli-
cation system by tightening the cone
point set screw "C" using a hex-
agonal male spanner.

K

L

→

Unscrew the cover "K" on the
position feedback.

→

Unscrew the cable gland "L".

→

Thread the cable through the cable
gland.

→

Wire according to the wiring
diagram for your version of the 1062:
See chap. „8 Installation and wiring“

.

→

Fasten the cable gland to ensure
tightness of the product.

7.4

fitting the position feedback with
stroke limiter to a pneumatic
actuator size 50 to 80mm

note

the tightness of the actuator is not guaranteed when the
transparent cap is removed.

▶ Prevent the projection of fluids into the actuator.
the tightness of the position feedback is not guaranteed
when the cover is removed.

▶ Prevent the projection of fluids into the position feedback.

english