English – Burkert Type 8642 User Manual
Page 46
Advertising

8642 - 45
english
FSAVE_TIME
Time in seconds after which the „Failsave“ action starts
after abortion.
The maximum value for this time is approx. 18 hours.
FSAVE_TYPE
Reaction on ”Fail Save”
0
=
valve retains the last state
1
=
valve switches according to FSAVE_VAL_D
2
=
valve becomes potential-free
FSAVE-VAL-D
The present discrete output value to use when failure
occurs.
SIMULATE
Enables the simulation of READBACK_D
CHECK_BACK
Information of the device
Bit
Information
0
in “Fail-save” position
8
Valve opens
9
Valve closes
16
The number of switching cycles pre-defined in
TRAVEL_COUNT_LIM has been exceeded
20
Time for opening exceeded
21
Time for closing exceeded
1 = active
0 = inactive
CHECK_BACK_MASK Definition of supported CHECK_BACK informtion bits
1 = supported
0 = not supported