Safetypositions

Key in recess for
actuating the Teach
function (keep
pressed for approxi-
mately 5 seconds)

Fig. 20: Teach function

Close the device (assembly tool: 674078

6)

).

Chronological description of the teach function:
• the bottom position is read in internally
• the pilot valve switches
• the actuator moves automatically to the top position
• the top position is read in internally
• the pilot valve is turned off
• the actuator moves back to the home position.

important:
When the teach function is activated the actuator cannot be
actuated via the AS-Interface or DeviceNet communication.

6)

The assembly tool (674078) is available from your Bürkert sales office.

11 safeTy posiTions

actuator

system

designation

safety positions after

failure of the auxiliary

power

electrical

pneumatic

up

down

single-acting

Control

function A

down

down

up

down

single-acting

Control

function B

up

up

up

down

double-acting

Control

function I

down

not

defined

Tab. 14: Safety positions