Structure and function of the modules

procedure when replacing a valve

CAuTIoN!

Only one valve may be removed at the same time.

•

During removal, observe that only the P channel is shut off! This means that a pressure on the working out-

•

puts A or B is released when the valve is removed. This also means that a connected actuator is also depres-
surized and a movement may be triggered as a result.

If there is a larger volume on the actuator side, attach a shut-off option for the working connections to prevent

•

the actuator from moving.

When the valve is removed, a relatively large amount of air is initially blown into the open for functional reasons, as
the P shut-off cannot close until the required pressure difference is reached. However, as the automatic shut-off
reduces the exhaust air significantly, only a residual leakage remains when the P shut-off is closed.

When installing the valve, ensure that the seal is inserted correctly.

→

Install the valve at the tightening torques indicated in the operating instructions.

→

When installing the valve, ensure that the working connections are also pressurized in the corresponding rest

→

position of the valve until it is switched over. The pressurization may cause a connected actuator to move.

Ensure that these movements of the actuator do not cause any damage or unwanted actions in the system.

→

Before changing the valve, we recommend bringing the system into an electrically safe basic state.