Adjustment and operation of the controller – Burkert Type 1094 User Manual
Page 23

23
Operation and function
adjustment and operation of the
8.4.
controller
To adjust the controller in a gasoline pump, all components, signal
lines and the gas meter from the calibration case must be connected
correctly.
side selection
Each side of the gasoline pump can be controlled separately via the
slide switch (side selection).
Side 1
Side 2
The appropriate side of the gasoline pump is
controlled by pushing the switch up or down.
Selecting the side of the gasoline pump
Fig. 11:
suB-d plug
(connection to the manual control unit type Mkne-1094)
The controller is operated and calibrated exclusively via the external
manual control unit Type MKNE-1094 which is connected to the con-
troller via a 9-pole SUB-D plug.
Configuration of the SUB-D plug:
pin
i/O
description
1
nc
–
2
OUT
Clock for serial communication
3
BIDIR
Data line
4
nc
–
5
PWR
GND
6
nc
–
7
PWR
+5 V
8
nc
–
9
nc
–
Configuration of the SUB-D plug
Table 4:
English
Type 1094 EV