Burkert Type 1115 User Manual

Page 13

Advertising
background image

13

150

UINT16

Mask configuration support / single controller

151

FLP

kp1

amplification heating / continuous

152

FLP

kp2

amplification cooling

153

FLP

Tn

reset time

154

FLP

Tv

derivative-action time

155

FLP

Ratio derivative-action time / delay time

156

FLP

Y0

operating point

157

FLP

Xtb

insensitiveness

158

UINT8

direction of effect

0:

positive direction of effect

1:

inverted direction of effect

160

UINT16

Mask configuration output

161

UINT8

Function output

0:

reserve

1:

2-point

2:

3-point

3:

3-point step (without external feedback)

4:

continuous

5:

position (with external feedback)

162

UINT8

Type continuous output

0:

0 - 10 V

1:

0 - 20 mA

2:

4 - 20 mA

163

UINT8

Pulse valve yes / no (with 2 point output)

0:

no pulse valve

1:

pulse valve

164

FLP

Ty

motor running time

165

FLP

Xsh

hysteresis

166

FLP

Xsd

insensitiveness

167

FLP

T+

cycle time heating

168

FLP

T-

cycle time cooling

169

FLP

Gt

gear lot

170

FLP

Olp

overlapping range

171

FLP

Y s

safety value

180

UINT16

Mask configuration binary input / output

181

UINT8

Function binary input

0:

no

(no function)

1:

alarm

2:

manual / automatic

3:

external / internal W (if index 71 = 1)

4:

safety value

182

UINT8

Effect binary input

0:

normal

1:

inverted

Advertising