Burkert Type 1115 User Manual

Page 24

Advertising
background image

24

Further information concerning the menus

M o d e

local

In the local mode, only data from digital units can be requested through the serial
interface. External data cannot be transmitted to the units.
The digital units can only be configurated and parametrated and the required
value can only be adjusted (at the controller) by using the unit`s keyboard and
not through the serial interface.

remote

In the remote mode , data can be transmitted in both directions through the
serial interface.
The digital unit can be configured and parametrated and the required value can
be adjusted using the serial interface.
In this case, the parametration and alteration of the required value cannot be
carried out through the unit`s keyboard.
If the operator mode is accessed through the remote mode by using the unit
keyboard, then the main configuration menu does not appear as usual, but rather
a menu item appears which permits the setting of the interface mode.
The configuration can be carried after the mode has been switched from remote
to local .

Baud rate

Bd: 4800

The baud rate equals 4800 baud.

BD: 9600

The baud rate equals 9600 baud.

This parameter can only be set by using the interface RS 232.

Parity check

Par: none

No parity check will be carried out.

Par: even

A check and/or an alteration will be carried out on an even parity.

Par: odd

A check and/or an alteration will be carried out on an odd parity.

This parameter can only be set by using the interface RS 232.

Address

Adr:

Address of the interface card
Address range with RS 232:

1 ... 32

Address range with RS 485 / Profibus:

0 .. 127.