Burkert Type 8793 User Manual
Page 152
![background image](/manuals/330165/152/background.png)
152
Auxiliary functions
If several diagnosis messages are available with different status signals, the status signal with the highest priority
is shown on the display.
Overview.of.the.status.signals.according.to.NE.107.(NE.=.NAMUR.recommendation):.
Priority
1
2
3
4
Status.signal
Description
Failure
Function check
Out of specification
Maintenance required
Table 77:
CONFIG.MSG; overview of status signals
The following status signals have been preset at the factory for the messages of the diagnosis functions:
Diagnosis.function
Status.signal.according.to.NE.107
Signal.
Miniature
Priority
SERVICE.TIME
Maintenance required
4
TRAVEL.ACCU
Maintenance required
4
CYCLE.COUNTER
Maintenance required
4
TEMP.CHECK
Out of specification
3
STROKE.CHECK
Out of specification
3
PV.MONITOR
Out of specification
3
POS.MONITOR
Out of specification
3
Table 78:
CONFIG.MSG; factory setting (Default)
Assignment.of.status.signals:
Key
Action
Description
/
Select
CONFIG.MSG
ENTER
Press
All activated diagnosis functions, which can output a message, are
displayed.
/
Select required diagnosis
function
ENTER
Press
The list of possible status signals is displayed.
/
Select required status signal
SELEC
Press
The selected status signal is now marked by a filled circle .
EXIT
Press
Acknowledgment and simultaneous return to the
CONFIG.MSG
menu.
The status signal is now assigned to the diagnosis function.
EXIT
Press
Return to the
DIAGNOSE main menu.
Table 79:
CONFIG.MSG; assignment of status signals
english
Type 8792, 8793