Installation

→

Lift the cover off.

→

Wire the connections of the additional limit switches (FC1 and FC2)
according to the circuit diagram figures (see “Fig. 2”

and “Fig. 3” ).

→

Tighten the cable gland after connecting the terminals.

→

Set the cover in place and screw it tight.

→

Reinstall the position indicator.

Only use 4 or 6 conductor cable with a diameter of 7 ... 12
mm for the ISO20 cable fitting.
Ensure that the cable in the ISO20 cable fitting is com-
pletely sealed when tightening the union nut.

7.3.1. setting the limit switches

The rotary actuator is supplied with the following factory
settings:
• The CLOSED limit switches are activated with the cams 2

and 4 (closed position).

• The OPEN limit switches are preset at a 90° rotation

angle.

The procedure for setting the limit switches is shown in “Fig. 4”

and

“Fig. 5”

.

Electronic card

Shaft

Motor

Body

Wrench (00679946)

Cam No. 4
Additional limit
switch CLOSED

clOsed

black

Cam No. 3
Additional limit
switch OPEN

Open

white

Cam No. 2
Motor limit switch
CLOSED

clOsed

black

Cam No. 1
Motor limit switch
OPEN

Open

white

Fig. 4: Setting the limit switches. Limit switches max. 250 V / 5 A

Setting in
clockwise direction
or setting in
counter clockwise
direction

Cams

Wrench

Adjustment
direction

Fig. 5: Setting limit switches in counter clockwise and clockwise

directions

english