Burkert Type 3003 User Manual
Page 15

15
Installation
7.4.
circuit board for actuator with
standard signal input
A
D
F
E
B
G
C
M
I
K
L
H
J
N
Fig. 6: Circuit board
A Electrical power supply
24 V AC/DC
H
K2 plug-in jumper
B Connection terminals of
the input signal
I
K3 plug-in jumper
C Connection terminals of
the feedback
J
Green and red LED
D MEM pushbutton
K
LED yellow: Indicates the
power supply
E CLOSE pushbutton
L
Potentiometer
F
OPEN pushbutton
M
Motor connection
G K1 plug-in jumper
N
Heat resistor connection
To prevent electromagnetic interference, shielded cables
must be used.
procedure:
→
Loosen the cable gland and feed the cable through.
→
Wire the signal transducer between terminals 15 and 16. Terminal
15 is the negative pole (-) and terminal 16 the positive pole (+).
→
Wire the position feedback sensor between terminals 13 and 14.
Terminal 13 is the positive pole (+) and terminal 14 the negative
pole (-).
→
Re-attach the cable gland.
If the connection voltage is 100 V to 240 V, a fuse must be
provided in the power supply.
english