Technical data
Type 8025 UNIVERSAL
88
88
76
ENTER
0....9
FLOW
25
40
Fig. 2: Dimensions of transmitter 8025 Universal, panel version [mm]
143
120
126
31.50
90
23
23
ENTER
0....9
FLOW
Fig. 3: Dimensions of transmitter 8025 Universal, wall-mounted
version [mm]
6.4
Electrical data
Power▶supply▶12-36▶V▶DC
•▶ filtered▶and▶regulated
•▶ SELV▶circuit,▶with▶a▶safe▶energy▶
level
•▶ max.▶tolerance▶12▶V▶DC:▶-5▶%▶or▶
+10%
•▶ max.▶tolerance▶36▶V▶DC:▶±10▶%
Power▶source▶(not▶provided)
•▶ Source▶with▶limited▶power▶in▶
accordance▶with▶§▶9.3▶of▶the▶
EN▶61010-1▶standard
•▶ or▶class▶2▶source▶in▶accordance▶
with▶the▶UL▶1310/1585▶and▶
EN▶60950-1▶standards
Power▶supply▶115/230▶V▶AC
•▶ frequency
•▶ supplied▶voltage
•▶ current
•▶ integrated▶protection
•▶ power
•▶ 50/60▶Hz
•▶ 27▶V▶DC,▶regulated
•▶ max.▶250▶mA
•▶ 250▶mA▶time▶delay▶fuse
•▶ 6▶VA