4 installation of a wall-mounted version, English, Remove▶the▶blanking▶strips▶covering▶the▶screws – Burkert Type 8035 User Manual

Page 20: Current source sink, Ao1) supply nc coil puls e input npn/pnp 2 1 3 pe, Fig. 12: installation of a wall-mounted version, Wire▶acc.▶to▶instructions▶in▶chap.▶ „7.6

Advertising
background image

18

Installationandwiring

Type 8025 /8035 Batch

7.4

installation of a wall-mounted
version

note

risk of material damage if the cable glands are not tightly
screwed on the housing

▶ Before▶installing▶the▶wall-mounted▶housing▶on▶its▶support,▶

tighten▶the▶nuts▶of▶the▶entry▶item▶of▶the▶cables▶glands▶at▶a▶torque▶

of▶1.5▶Nm.

The▶device▶in▶a▶wall-mounted▶version▶has▶4▶holes▶in▶the▶bottom▶of▶
the▶housing.

Remove▶the▶blanking▶strips▶covering▶the▶screws.

Blanking▶strips

ENTER

0....9

FLOW

Nut▶of▶the▶entry▶item

Loosen▶the▶4▶screws▶and▶open▶the▶cover▶to▶get▶access▶to▶the▶
holes▶[1].

1

1

1

1

106 mm

230V

L N

230V

T 250 mA

5 6 7 8 9 10

L N

230V

CURRENT

SOURCE

SINK

BINARY

PE

PE

PE

PE

DI1

DI2

DI3

DI4

DO4

ISOG

FLOW

SENSOR

L+

L-

PE P- P+

NC

Iout

PULSE

DO1

Supply

12..36Vdc

Univ
Batch

(AO1)

SUPPLY

NC

COIL

PULS

E

INPUT

NPN/PNP

2

1

3

PE

+

-

SENSOR

SUPP

LY

LOAD

+5V

L+

(L+)-12V COIL/PNP

39K

470

2.2K

SENSOR TYPE

COIL

NPN/PNP

DO2

DO3

OF

FO

N

106 mm

Fig. 12: Installation of a wall-mounted version

Secure▶the▶housing▶to▶the▶support▶respecting▶the▶dimensions▶
indicated▶in▶„Fig.▶12“.

Wire▶acc.▶to▶instructions▶in▶chap.▶„7.6“.

Close▶the▶housing▶and▶tighten▶the▶4▶screws▶of▶the▶cover.

7.5

installation of a 8035 Batch

7.5.1 recommandations for installing the

8035 Batch on the pipe

The▶electronic▶module▶SE35▶Batch▶can▶be▶installed▶on▶a▶pipe▶by▶
using▶a▶sensor-fitting▶S030.

Choose▶an▶S030▶fitting▶appropriate▶to▶the▶velocity▶of▶the▶fluid▶
inside▶the▶pipe.

English