52

Adjustmentandcommissioning

Type 8025 /8035 Batch

•▶ If▶the▶generation▶of▶alarms▶(alarm▶"DURING")▶for▶problems▶occuring▶during▶a▶dosing▶has▶been▶activated,▶an▶alarm▶is▶generated▶if▶there▶is▶no▶

flow▶rate▶measured▶in▶the▶pipe▶whereas▶the▶valves▶are▶open.▶Refer▶to▶the▶detailed▶operating▶instructions▶to▶solve▶the▶problem.

•▶ If▶the▶generation▶of▶alarms▶(alarm▶"AFTER")▶for▶problems▶occuring▶at▶the▶end▶of▶the▶dosing▶has▶been▶activated,▶an▶alarm▶is▶generated▶if▶there▶

is▶still▶flow▶in▶the▶pipe▶whereas▶the▶valves▶are▶closed.▶Refer▶to▶the▶detailed▶operating▶instructions▶to▶solve▶the▶problem.

BAtCH M

0100.0L

OK Y/N

89.2 L

Enter▶a▶dosing▶quantity▶(value▶between▶0.0001▶and▶99999▶dosing▶units,▶where▶the▶units▶have▶been▶
selected▶in▶the▶"UNIT▶parameter)▶higher▶or▶equal▶to▶6▶divided▶by▶the▶fitting▶K▶factor▶(in▶pulse/litre).

Confirm.

Choose▶"OK▶Y"▶to▶start▶the▶dosing.

Confirm.

The▶dosing▶quantity▶is▶counted▶down▶until▶0▶(the▶dosing▶units▶blink).

To▶read▶the▶flow▶rate▶measured▶in▶the▶pipe,▶press▶

▶or▶

0......9

.

To▶read▶the▶total▶dosing▶quantity,▶press▶

▶or▶

0......9

▶once.

To▶interrupt▶the▶dosing,▶see▶„Fig.▶37“.

Confirm.

Process▶
level

0.1 L

When▶the▶dosing▶is▶finished:
•▶ the▶dosing▶units▶do▶not▶blink▶any▶more,
•▶ and▶the▶valves▶are▶closed.

To▶go▶back▶to▶the▶Process▶level▶in▶order▶to▶start▶a▶new▶dosing,▶press▶

ENTER

.

Fig. 36: Doing a dosing, in dosing mode "LOC. MANU."

English