42

Installationandwiring

Type 8025 /8035 Batch

7.6.12 Wiring the relay outputs Do2 and

Do3 of a compact, a panel-mounted
or a wall-mounted version

To▶carry▶out▶a▶dosing,▶connect▶a▶valve▶to▶the▶relay▶output▶
DO2.

The▶device▶can▶control:
•▶ either▶a▶dosing▶with▶a▶single▶valve▶connected▶to▶the▶relay▶output▶

DO2.

•▶ or▶a▶dosing▶with▶2▶valves▶connected▶to▶the▶relay▶outputs▶DO2▶and▶

DO3.▶In▶this▶case,▶connect▶the▶main▶valve▶(for▶the▶highest▶flow▶
rates)▶to▶output▶DO2▶and▶the▶auxiliary▶valve▶(for▶low▶flow▶rates)▶to▶
output▶DO3.

If▶a▶single▶valve▶is▶used,▶connect▶a▶load▶to▶relay▶output▶DO3▶suited▶
for▶the▶configuration▶of▶the▶output.

FLOW

SENSOR

SUPPLY

NC

COIL

PULSE INPUT

NPN/PN

P

2

1

3

PE

+

-

DO2

DO3

OF

FO

N

230 V AC

m

3 A

3 A

230 V AC

Fig. 34: Wiring of the DO2 and DO3 relay outputs

To▶configure▶the▶relay▶output▶DO2,▶Refer▶to▶the▶detailed▶oper-
ating▶instructions.

To▶configure▶the▶relay▶output▶DO3,▶Refer▶to▶the▶detailed▶oper-
ating▶instructions.