Relay 1 operator: ( a &(b | c) ) – GF Signet 8900 Multi-Parameter Controller User Manual

Page 32

Advertising
background image

32

Signet 8900 Multi-Parameter

10

5

ela

ut

ut

ate

0 t

00 Pul

e

min

en

int

Pulse rate

0 pulses

100 pulses

Starting

int

Proportional Pulsing
•

Proportional Pulse mode varies the frequency of pulses in direct
proportion to minimum and maximum setpoints.

•

The 8900 does not allow use of this mode for Pressure applications.

Example:
•

The output will be 0 pulses/min. at process values less than 5.0.

•

The output will be 50 pulses/min. when the process value is 7.5.

•

The output will be 100 pulses/min. at process values above 10.

0

20

0

0

80

100

elay Pulse idth

as a of elay period

P M
minimum
range

P M
maximum
range

elay is

always

elay is

always

Process value

Pulse Width Modulation
•

PWM automatically varies the ratio of ON time to OFF time
proportional to minimum and maximum range settings.

•

The relay period is the sum of the time a relay is ON and the
time it is OFF.

•

Relay pulse width is the time the relay is ON.

•

The 8900 must be programmed with the relay period, and with
the low and high setpoints.

•

The 8900 does not allow use of this mode for Pressure
applications.

Example:
•

The pulse width will be 0% of the relay period (relay always OFF)
when the process value is less than the minimum range.

•

The pulse width will be 100% of the relay period (relay always
ON) when the process value is greater than the maximum range.

•

The pulse width will be 60% of the relay period when the process
value is at 60% of the span between the minimum and maximum
range.

Volumetric Pulse
•

A pulse is generated each time a specifi ed volume of fl uid is
registered. For fl ow inputs only.

Totalizer Volume
•

Relay activates and latches when a specifi ed volume of fl uid
is registered. For fl ow inputs only.

•

Total Volume mode counts the TOTALIZER Units until the
setpoint volume is reached, then activates the relay until the
resettable totalizer is reset.

•

If the Resettable Totalizer reading is greater than the
setpoint, the relay will be activated immediately. The relay
will be relaxed when the totalizer is reset to zero.

•

This mode is useful to trigger a reminder when a process is
due, as for a backwash cycle or fi lter change.

Advanced
•

Relay is activated when a set of three conditions (a, b and c)
are met. See detailed explanation in Section 11.2.

Relay 1 Operator:

( a &(b | c) ) >