Table 8 – Hach-Lange SC 200 Modbus Module User Manual User Manual

Page 12

Advertising
background image

Table 7 Classified status 3 – register 49933 (continued)

Bit

Error

Note

3

–

–

4

Measurement 8 Quality Bad

Precision of measurement is out of
specified limits.

5

Measurement 8 Low Limit

Measurement is below measurement
range.

6

Measurement 8 High Limit

Measurement is above measurement
range.

7

Measurement 9 Quality Bad

–

8

Measurement 9 Low Limit

–

9

Measurement 9 High Limit

–

10

Measurement 10 Quality
Bad

–

11

Measurement 10 Low Limit

–

12

Measurement 10 High Limit

–

13

Measurement 11 Quality
Bad

–

14

Measurement 11 Low Limit

–

15

Measurement 11 High Limit

–

Table 8 Classified status 4 – register 49934

Bit

Error

Note

0

Reserved for future use

Fixed at 0

1

–

–

2

–

–

3

–

–

Table 8 Classified status 4 – register 49934 (continued)

Bit

Error

Note

4

Measurement 12 Quality
Bad

Precision of measurement is out of
specified limits.

5

Measurement 12 Low Limit

Measurement is below measurement
range.

6

Measurement 12 High Limit

Measurement is above measurement
range.

7

Measurement 13 Quality
Bad

–

8

Measurement 13 Low Limit

–

9

Measurement 13 High Limit

–

10

Measurement 14 Quality
Bad

–

11

Measurement 14 Low Limit

–

12

Measurement 14 High Limit

–

13

Measurement 15 Quality
Bad

–

14

Measurement 15 Low Limit

–

15

Measurement 15 High Limit

–

12 English

Advertising