Charging programs, Connect the cables, 12v 24v – CTEK MXTS 70 User Manual

Page 4

Advertising
background image

6 • EN

5

3

4

ChARGING PROGRAMS

Choose program by pressing the MODE-button.

Adjust parameters according to "CHARGING" (6–8).

Press START/PAUSE button to start the selected program.

The table explains the different Charging Programs:

Program

Battery Size

(Ah)

Explanation

Temp range

NoRmAl

40–1500Ah

20–750Ah

Use for WET and MF batteries.

-20°C–+50°C

(-4ºF–+122ºF)

Ca/Ca

40–1500Ah

20–750Ah

Use for Ca/Ca batteries. Use Ca/Ca-program to maximize charge with

minimum loss of fluid. Including RECOND step. Recond your battery once

per year and after deep discharge to maximise lifetime and capacity.

-20°C–+50°C

(-4ºF–+122ºF)

AGm/GEl

40–1500Ah

20–750Ah

For AGM and GEL batteries which are recommended to receive lower

voltage charge.

-20°C–+50°C

(-4ºF–+122ºF)

AGm PoWER

40–1500Ah

20–750Ah

Use for AGM batteries which are recommended to receive higher voltage

charge.

-20°C–+50°C

(-4ºF–+122ºF)

SuPPly

40–1500Ah

20–750Ah

Use as 12V/24V power supply or use for float maintenance charging when

100% capacity of the battery is required. Supply program activates step 7

without time or voltage limitation. Supply program enables the charger to

deliver 70A/12V or 35A/24V for 30 seconds.

-20°C–+50°C

(-4ºF–+122ºF)

CONNECT ThE CABLES

If the battery clamps are incorrectly connected, the reverse polarity protec-

tion will ensure that the battery and charger are not damaged.

1. Connect the battery cable, including the temperature sensor, to the

charger

2. Connect the mains cable to the charger

3. Connect the red clamp to the battery´s positive pole.

4. Connect the black clamp to the vehicle chassis remote from the fuel pipe

and the battery.

5. Connect the charger to the wall socket

6. Disconnect the charger from the wall socket before disconnecting the

battery

7. Disconnect the black clamp before the red clamp

WARNING!

Risk for short circuiting the battery cables. Connect charger cables

to the charger before connecting the battery

WARNING!

Risk for electrical shock if touching positive and negative terminals

when charging

1

+

+

2

12V

24V

Current

Battery size Min

Battery size Max

Current

Battery size Min

Battery size Max

20A

40Ah

100Ah

10A

20Ah

50Ah

30A

60Ah

150Ah

15A

30Ah

75Ah

40A

80Ah

200Ah

20A

40Ah

100Ah

50A

100Ah

-

25A

50Ah

-

70A*

100Ah

-

35A*

50Ah

-

• Using higher current than recommended may result in batteries not being

completely charged.

•Using lower current than recommended will prolong the charging time.

• The currents are the maximum recommended current for battery charg-

ing. If a parallel consumer is connected then the current setting could be

increased with this current value.

• Some battery manufacturer could recommend different values. Please

check with the manufacturer if uncertain. The main recommendations are

that Gel batteries should be charged in the lower current range, Power

AGM’s in the upper range and most other battery types in the mid-range.

*) 70/35A Could only be selected for Supply program

Some vehicles may

have positively

earthed batteries

3. Connect the black

clamp to the battery´s

negative pole.

4. Connect the red clamp

to the vehicle chassis

remote from the fuel

pipe and the battery.

7. Disconnect the red

clamp before the black

clamp.