Appendix B: Altos R300 Rack installation guide

106

Elevated Operating Ambient Temperature

The maximum operating temperature of the system is 35 °C (95°F).
Careful consideration should be given to installing the system in
an environment compatible with the 35 °C (95°F) maximum
ambient temperature.

Reduced Airflow

The amount of airflow required for the safe operation of the
equipment should not be compromised when installing the system
in a rack.

Mechanical Loading

Exercise care when mounting the system in a rack to avoid any
accidents.

Circuit Overloading

Appropriate consideration should be given when connecting the
supply circuit to the system to avoid any circuit overload. The
system nameplate rating should be used when addressing
concerns about circuit overload.