Laurel Electronics Modbus Protocol For Series 2 Laureate Digital Panel Meters, Counters, Timers & DIN-Rail Transmitters User Manual
Page 29

- 29 -
7 = Remote Display, Value
8 = 1st Value in String
9 = 2nd Value in String
A = 3rd Value in String
B = 4
th
Value in String
C = Remote Display using Start, Stop, Skip,
Show Characters
78
004E Lockout 1
0 = Enabled, 1 = Locked out
Bit 0
Filter
Bit 1
Gate Time, Timeout, Batch, Preset, Pulses, Cutoff
Bit 2
Setup, Config, Display Number
Bit 3
Input Type
Bit 4
Setpoint Programming
Bit 5
Alarm Config, Deviation / Hysteresis
Bit 6
Scale, Offset, Resolution, 2 Coordinates
Bit 7
Slope, Decimal Points
79
004F Lockout 2
0 = Enabled, 1 = Locked out
Bit 0
Change Item# displayed
Bit 1
Calibration
Bit 2
Serial Comm Config
Bit 3
Analog Out Scaling & Setup
Bit 4
Front Panel Meter Reset
Bit 5
Front Panel Function Reset
Bit 6
View Setpoints
Bit 7
View Peak
80
50
Batch
Operation
Bit 0
0 = Display “rEADy” after Reset
1 = Start
Bit 1
0 = Item2 is Grand Total
1 = Item2 is Total Number of Batches
Bit 2
0 = Gate Time resets
1 = Control Input 2 resets
Bit 3
0 = Reset to Zero, Count Up
1 = Reset to SETPT1, Count Down
Bits 5:4 Residual Input
0,2 = Input Discard, Grand Total Discard
1 = Input Accept, Grand Total Discard
3 = Input Accept, Grand Total Accept