Laurel Electronics Modbus Protocol For Series 2 Laureate Digital Panel Meters, Counters, Timers & DIN-Rail Transmitters User Manual
Page 8

- 8 -
E1
E4
E6
E3
E2
a
b
c
a
b
a b
c
d
a
b
c
d
Serial Signal
Duplex
Jumpers
Termination Resistor*
Full
None
E6 a = Transmit
E6 c = Receive
RS485
Half
E6 b + d**
E6 c
RS232
Full
None
None
Serial Signal
Duplex
Jumpers
Termination Resistor*
Full
None
E6 a = Transmit
E6 c = Receive
RS485
Half
E6 b + d**
E6 c
RS232
Full
None
None
*
The termination resistor jumper settings should only be selected if the transmitter is the last
device on an RS485 line longer than 200 feet (60 m).
** Attempting to draw more than the rated current will shut down the output.
To reset communications to 9600 baud, command mode, Custom ASCII protocol, and Address 1,
place a jumper at E1 and power up the transmitter.
Analog Output
Jumpers
Current
E2 a + d
Voltage
E2 b + c
Excitation Output*
Jumpers
5V, 100 mA
E3 a + c; E4 a
10V, 120 mA
E3 a + c; E4 b
24V, 50 mA
E3 b, E4 none
* The termination resistor jumper
settings should only be selected
if the transmitter is the last device
on an RS485 line longer than 200
feet (60 m).
** Or jumper external BTX to BRX
and ATX to ARX (same effect as
internal jumpers).