5 pcs floating point-to-integer conversion – Micromod Micro-DCI: 53MC5000 PLC AND PRINTER INTERFACES User Manual
Page 27

3.5 PCS FLOATING POINT-TO-INTEGER CONVERSION
In the PCS, floating point numbers are converted to 16 bit unsigned integers before being written
to the PLC. When converted from a floating point number to a 16 bit unsigned integer by the PCS,
the following rounding procedure applies:
PCS Range
Conversion to PLC Integer Value
−∞ to <1
0
1 to <32,769
Rounded down to nearest integer
32,769 to <65,536
Rounded down to nearest even integer
65,536 to +
∞
All values are stored as 65,535
Data read from the PLC (with the exception of OPTO 22) is considered to be 16 bit unsigned inte-
gers and is converted to floating point numbers by the PCS as follows:
PLC Integer
PCS Floating Point Conversion
0 to 32,768
Unchanged
32,769 to 65,535
Rounded down to nearest even integer
It should be noted that a process measurement range (e.g., temperature) with negative numbers
is possible using an algorithm in the PLC that converts the range to all positive numbers; an F-TRAN
routine can be written to perform the same task in the PCS.