6.3 RS-232/485 ITB-PLC CABLES
A custom RS-232 cable is required for point-to-point connection from the RS-232/485 ITB J1 to the
PLC. The recommended cable for this PLC application is illustrated in Figure 6-3. In the figure,
one end of the cable has a nine pin male plug that connects to J1 of the RS-232/485 ITB and the
other end has a 25 pin male or female plug as required by the PLC.
For multidrop installations, the standard four wire bundle with shield is used to connect TB2 of the
RS-232/485 board to the Modbus PLC RS-422 input. The TB2 lug connections are illustrated in
Figure 6-4. The maximum cable length for RS-485 (422) is 4000 feet (1219 m).
RS-232/485 ITB, J1
MODBUS PLC
(FEMALE DB-9
(MALE/FEMALE, DB-25
CABLE END)
CABLE END)
(MODEL 884
MODBUS PLC)
RxD (IN)
2
2 TxD
TxD (OUT)
3
3 RxD
GND
5
7 GND
7
4 RTS
8
5 CTS
6 DSR
20 DTR
(USED WITH MODBUS POINT-TO-POINT INSTALLATIONS)
Figure 6-3. RS-232/485 ITB J1 to Modbus PLC Cable
RS-232/485 ITB TB2
MODBUS
CONNECTION
CONNECTION
RECEIVE (R-)
1
TRANSMIT (T-)
RECEIVE (R+)
2
TRANSMIT (T+)
TRANSMIT (T-)
3
RECEIVE (R-)
TRANSMIT (T+)
4
RECEIVE (R+)
SHIELD
5
GROUND
(USED WITH MODBUS MULTIDROP INSTALLATIONS)
Figure 6-4. RS-232/485 ITB TB2 to Modbus PLC Cable
53MC9015 53MC5000 PLC and Printer Interfaces
6-2