Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) Algorithms, Tables and Sequential Logic Functions User Manual
Page 136

Logic Functions - Book 2
SEQUENCE BLOCK
10-16
00
Version (VERSION) ...............................................................................................................--R
The valid version is 1.
01
Block Length (BLKLEN) .......................................................................................................--R
02
Block State (STATE).......................................................................................................... CWR
All block state changes are reported as informational events. See IB-23G600 Section 2.4.1,
State Changes for additional information.
RUN
0
Normal Operation. Block is executed.
HOLD
1
Block is not executed. Qualities retain previous values.
OFF
2
Block is not executed. Qualities will be BAD.
DEBUG
3
Block is not executed. No fields are updated. All attributes are
writeable.
03
Bad Inputs (BADINP)......................................................................................................... CWR
This block runs with bad inputs REJECTED or.ACCEPTED See IB-23G600 Section 2.3.2,
Data Quality for additional information.
REJECTED
0
Operation of the Sequence block is affected by the quality of its
inputs as described in Section 10.2.1, Block Operation.
ACCEPTED
1
Bad inputs are ignored, and normal RUN processing occurs. There
is no check on input quality and output quality is set to good.
04
Diagnostic Group (SUPPGRP)......................................................................................... CWR
The diagnostic error reported by this block can be grouped for System Event block control of
its reporting. The selections are:
NONE
0
No group assigned.
1 to 7
Defines the diagnostic group number for the diagnostic suppression group
controlled by the System Event block.
05
Bad Input Error (IERRS) ................................................................................................... CWR
When the Bad Input (Attribute No. 03) is set to REJECTED, and bad quality is detected in an
external step input or transition expression input, the block reports the diagnostic error as BAD
INPUT ERROR, and takes action in accordance with the configuration of Attribute No. 41,Bad
Input Action.
ENABLED
0 Input error is enabled
SUPPRESSED 1 Input error is suppressed.
06
Input Error Unacked (CERRU) .........................................................................................– WR
If the bad input error diagnostic is enabled, the unacknowledged status indicates if the
diagnostic is or is not acknowledged. Only writeable in DEBUG.
NO
0
Diagnostic error is acknowledged.
YES
1
Diagnostic error is unacknowledged.