Logic Functions - Book 2

CONFIGURING THE SEQUENCE BLOCK

11-9

Defining the I/O Modules
The I/O modules required for this application example are as follows:

•

Three digital input modules to accept the signals from the high level switch, low level
switch, and the feedback signal from the drain valve.

•

One RTD module to accept the product temperature signal (an RTD input function block
is required to condition the signal from the RTD module).

•

Two digital output modules to generate the open and close signals for the fill valve and
drain valve.

See IB-23G600 for more information about I/O modules. Define the I/O modules using the
step-by-step instructions in Table 11-7.

Table 11-7. I/O Module Definition Procedure

Step

Procedure

Comments

1

From the Algorithm window, select the following icons
and place them in the workspace:

3 DIM (Digital Input Modules)
1 WRIM (3-Wire RTD Module)
2 DOM (Digital Output Modules)

2

Double click to query the first DIM. The Digital Input
Module Block properties appear.

3

Select the Name field and type the name LSL-1M. Also
enter the proper slot number for the module.

The default values for all other block
attributes are acceptable without
change. Note that it is not necessary
to specify a number in the Slots field.
The slot location can also be defined
using the I/O Graphic display.

4

Select OK.

Note that the assigned tag name now
appears in the DIM block.

5

Using the procedure of Steps 2 through 4, assign
names to each remaining I/O module as follows:

Second DIM:

LSH-1M

Third DIM

DrainingM

WRIM

TE

First DOM

Fill

Second DOM

Drain

6

From the Algorithm window, select the following icons
and place them in the workspace. Assign names to
each block as follows

First DI (Digital Input Block)

LSL-1

Second DI (Digital Input Block)

LSH-1

Third DI (Digital Input Block)

Draining

1 RTI (RTD Input Block)

TI

9

Select the RTI block Temperature Scale Field and
select Fahrenheit.

Default entries for all other attributes
are acceptable without change.

10

Select enter to return to the workspace display.