Logic Functions - Book 2
SUPERVISORY MESSAGE BLOCK
8-81
For other instrument types the attribute address is [Block number],[byte offset].
Use SETENTRY input for SET message types to connect internal attribute.
Data Conversion
Specifies the type of data conversion to be performed prior to sending
or after receiving the message. Valid types of conversions are:
millisecond time / time, floating Point / continuous, and NONE.
Range..................................................................................................................................C – –
Applies to continuous and floating-point data only. Enter range in floating point. Floating point
values sent (write message types) to instruments other than MODCELLS will be converted to
continuous values using these ranges before being sent. Continuous data being received (in
response to a read request) will be converted to floating point values using these ranges
before being stored.
Bottom
Indicates the 0% value (low). Default is 0.000.
Top
Indicates the 100% value (high). Default is 100.00.
Maximum Data Field Size..................................................................................................C – –
Indicates the maximum number of bytes or characters the data field can take. Valid values
are 1 to 126. This parameter applies only when sending or receiving Hex bytes or ASCII
characters.
Initial Data Type .................................................................................................................C – –
Indicates the type of data being entered in the Initial Data field (Floating-Point, ASCII,
Millisecond Time, Hex, Count, Discrete, Short State, Date, and Long State).
02
State (STATE).....................................................................................................................CWR
All block state changes are reported as informational events. See Section 2.4.1, State
Changes for additional information.
RUN
0
Normal Operation. Block is executed.
HOLD
1
Block is not executed. Qualities retain previous values.
OFF
2
Block is not executed. Qualities will be BAD.
DEBUG
3
Block is not executed. No fields are updated. All attributes are
writeable.
03
Bad Inputs (BADINP) .........................................................................................................CWR
See Section 2.3.2, Data Quality for additional information.
Rejected
0
Block checks Send Input and Data Input quality and will only run its
algorithm if input is good. If the quality of the Send Input is bad, the
block will not begin the message transaction. If the quality of the
Data Input is bad, the block will not begin the message transaction.
Accepted
1
Block runs its algorithm without a check on input quality and result
quality.
04
Diagnostic Group (SUPPGRP) .........................................................................................CWR
The diagnostic error reported by this block can be grouped for System Event block control of
its reporting. The selections are:
NONE
No group assigned. Read as 0.
1 to 7
Defines the diagnostic group number for the diagnostic suppression group
controlled by the System Event block.