Micromod MOD: 30ML and Modcell Maintenance for 2001N, 2002N, and 1800R User Manual
Page 84

MOD30ML and Modcell Maintenance Manual
DIAGNOSING SHUTDOWN FAULTS
3. With power off, install the memory module in an operable spare instrument (either
MODCELL or MOD 30ML).
4. Apply power to the instrument.
5. Start the Application Builder Software. If communication to the instrument is via an RS-
232 or RS-485 port, the default parameters (9600 baud, no parity, 8 data bits, 1 stop bit)
must be used. See Section 3 for the software startup procedure.
6. Access the status display in the application builder.
7. On the Instrument Status display command line, type the command R SD M and click on
ENTER. A display providing shutdown data appears. A form illustrating this display with
blank data fields is provided at the end of this section.
NOTE: If a facility for printing the display screen is available, it can be used to generate a
copy of the shutdown data.
8. Make a copy of the form and fill in the blank fields on the copy using the data from the
display.
9. Copy the Catalog number and Version number from the identity module in the failed
instrument onto the shutdown data form.
10. Keep a copy of the completed shutdown information for future reference.
6 -5