Rs422 termination, Standard rs422 “y” connection – Nitek DL1142 User Manual

Page 4

Advertising
background image

4

Standard RS422 “Y” connection

RS422

Twisted Pair

up to 12,000 ft

Any standard RS422

input device

Any standard RS422

output device

NITEK

TM

DL1142

wall transformer

(included)

Continue the RS422

chain on to other standard

RS422 devices

To “Y” off the RS422 signals put the incoming (source) RS422
and outgoing RS422 (going to next device) wires into the
same terminals. The total length of the standard RS422 chain
can be up to 4,000 feet.

When connecting the DL1142 in a “Y” configuration; that is, using
the DL1142 to split off a RS422 signal; the source RS422 data can
be continued on down a chain of units. To do this put the source wire
and the continuing wire connection into the “RS422 IN” connec-
tions.

RS422 Termination

Remove the slide off cover on the bottom of the DL1142 to access
its termination jumper. The RS422 termination should be used in
accordance with EIA standards regarding RS422 termination.

These are only a few of the many ways of using the DL1142 shown
here. If you need additional help you may call the NITEK

®

Technical

Department at 800-528-4343.