Introduction

The Fulton Pulse water heater is an
automatic gas fired, direct vent water
heater. This water heater utilizes the pulse
combustion principle. It requires no
conventional burner controls, no pilot and
no flue or chimney. The combustion
components are of integral design with the
heat exchanger. For combustion, the water
heater uses 100% outside air supplied
through schedule 40 PVC pipe.

The products of combustion are vented
outdoors through non-corrosive venting
materials which will withstand 480°F
(249°C) temperatures. These pipes can be
routed either through a roof or through the
side wall of a building. Each water heater
is built to ASME and CSD-1 Codes,
hydrostatically tested, test fired, and
shipped as a complete packaged unit.
Gas, water, and electrical connections are
similar to conventional water heaters.

All installations must be in accordance with
the American National Standard “National
Fuel Gas Code,” latest edition, and with
the requirements of local utilities or other
authorities having jurisdiction. Such
applicable requirements take precedence
over the general instructions herein.

Since an external electrical source is
utilized, the water heater, when installed,
must be electrically grounded in
accordance with the National eectrical
Code, ANSI/NFPA 70-latest edition.

In some cases the approval authority may
insist that the installation conform to the
American Society of Mechanical Engineers
ASME safety standard for controls and
safety devices for automatically fired water
heaters, or CSD-1.

In Canada, gas installations must be in
accordance with the current CAN/CGA
B149.1 and .2 and/or local codes.
Electrical installations must be installed in
accordance with the current CSA C22.1
Canadian Electrical Code and/or local
codes.

The following items
are standard trim
for Fulton Pulse
water heaters:

Full Modulation with a 5:1 turndown ratio
Fully Insulated
Microprocessor Based Control - 120 volt
Low Water Cutoff (Probe Type)
Control Panel Completely Wired with
Diagram
Operating Temperature Control
Hi-Limit Temperature Control w/ Manual
Reset
Air Pressure Switch
Spark Ignition
Main Motorized Gas Valve
Main Gas Pressure Regulator
Manual Lubricated Gas Cock
Second Gas Valve (Solenoid)

Included with and
packaged separately
with each water heater
are the following
components:

ASME Pressure Relief Valve
Pressure-Temperature Gauge
Air Intake and Exhaust Pipe Adaptors
Installation, Operation, and Maintenance
Manual
Elastomer Coated Fiberglass Cubes
Gas and Water Flex Connectors
Intake and Exhaust Mufflers

Optional Accessories

Condensate Liquid Drainer
Flex Connectors
Spring Mounts

Installation

General specifications and information about Fulton
Pulse Potable Water Heaters:

Models

PDWH750

PDWH1000

BTU/HR. Input

750,000

1,000,000

BTU/HR Output*

660,000

880,000

Fuel

NG/LPG

NG/LPG

Approx. Dry Weight

1,800 lbs.

1,400 lbs.

Approx. Operating Weight

2,150 lbs.

2,150 lbs.

Floor Loading

300 lbs/ft2

300 lbs/ft2

Power Required

120/60/1

120/60/1

Min. Required

7" W.C.NG

7" W.C. NG

Gas Pressure

11" W.C. LPG

11" W.C. LPG

Max. Amp Draw (F L.A.)

4.0

4.0

MAWP

160 PSI

160 PSI

Water heater Width

27.5 IN

27.5 IN

Water heater Height

76 IN

76 IN

Water heater Depth

37.8 IN

37.8 IN

GPH @100°F
Temperature Rise

790

1055

Note: *Based on 40°F in -140°F out.