Maintenance – Fulton Pulse DWH (PDWH) Domestic Water Heater User Manual

Page 39

Advertising
background image

Maintenance

Troubleshooting

This troubleshooting guide will assist in the diagnosis and correction of minor field problems. It should be used in conjunction with
the unit wiring diagram. In any case requiring additional assistance, the Fulton Service Department should be contacted.

Problem

Cause

Check

Starting or Purge Failure

Power Supply

Check fuse or circuit breaker. Reset or replace, as
necessary.

On/Off Switch

For all models check to see if on/off switch is illuminated.

Bad Air Switch

Try adjusting sensitivity of switch or replace.

Bad Fan

Check fan for operation. Replace if necessary.

Flame Rod (Option)

Check for carbon buildup, cracks in porcelin.

Main Control

Check for bad ground, or bad control.
Replace control.

Plugged Air Inlet

Check for blockage of air inlet line and remove.

Spark Plug

Check for carbon build up, moisture, cracks in
porcelain. Check for proper gap (.050" to .060"
for Champion sparkplug). Clean or replace as
necessary.

Loose Wire Connection

Check connections to all components.

Temperature Control

Check that the operating temperature control is set
higher than temperature of the water heater water.

Loose Tubing

Check to see if the copper tubing on the air valve
housing is securely connected.

Flame Failure

Power Supply

Check fuse or circuit breaker. Reset or replace
as necessary.

Main Control

Check for bad ground or bad control. Replace if
necessary.

Proof of Flame Switch

Check adjustment of pressure switch No. 2. It
should be set at 1.5" W.C. Replace if necessary.

Flame Rod (Option)

Check for carbon buildup, cracks in porcelin.

Loose Wire Connection

Check connections to all components.

Air Flappers

Check to see if the flappers on the air valve plate
are placed correctly (covering the holes).

Gas Flappers

Check to see if the flappers on the gas valve plate
are placed correctly (covering the holes).

Plugged Exhaust Line

Check for a blockage of the exhaust piping and
remove.

In All Cases:

Reset main control in panel box on flame failure.

Poor Combustion

Air Flappers

Check to see if the flappers on the air valve plate
are placed correctly (covering the holes).

Gas Flappers

Check to see if the flappers on the gas valve plate
are placed correctly (covering the holes).

Plugged Air Inlet

Check for blockage of air inlet line and remove.

36-PDWH