Installation

Figure 5b

Sequence of Operation

1. Turn on main breaker.
2. Low water safety relay (LWSR) is

energized when the main breaker is
turned on. (Red light on the water
heater panel is lit and if the optional
alarm is provided, alarm will go off.
Current is not allowed to pass to the
high limit temperature control until a)
the probe in the water heater shell
senses the water and b) the manual
reset switch is reset. If a and b are
both satisfied, the red light is turned
off.

3. High limit temperature control allows

current to pass to the next control if
the temperature in the water heater
water is not causing the control to
open the circuit.

4. Burner switch is then closed to ener-

gize the operating temperature con-
trol. (Green light on the panel is lit).

5. Operating temperature control

allows current to pass to the auto-
matic control relay if the temperature
of the water is not causing the
control to open the circuit.

6. 120V power is input to the automatic

control relay (RM7865A).

7. Purge blower is energized for 35

seconds.

8. Purge fan switch is made, signaling

the control to proceed.

9. Spark plug is energized.

10. Gas valve is energized.
11. Pressure sensing switch is made

(proof of flame) allowing sequence
to continue.

12. Pulse combustion will continue

until one or more of the following
things happen:
A. Operating temperature control is

satisfied.

B. High limit temperature control is

satisfied.

C. Low water safety relay loses

water on probe.

D. Burner switch is turned off.
E. Main breaker is turned off.

Glossary
AC

— Audible Alarm Control

(Optional)

ACR

— Automatic Control Relay

(7800 series)

BM

— Purge Fan Motor

BS — Burner

Switch

CR — Control

Relay

HLTC — Hi Limit Temp. Control
LW

— Panel Light (Low Water

Indicator)

LWCP — Low Water Cutoff Probe
LWRS — Low Water Reset Switch
LWSR — Low Water Safety Relay
GV

— Main Gas Valve

OTC

— Operating Temp. Control

PFS

— Purge Fan Switch

PL

— Panel Light (Power On Green)

PSS

— Pressure Sensor Switch No. 2

RC — Relay

Coil

SP — Spark

Generator

S.P.

— Spark Plug

TB-H — Terminal Block (Hot)
TB-N — Terminal Block (Neutral)