Installation – Fulton Alliance (FT-HC) Horizontal Coil Thermal Fluid (hot oil) Heater User Manual

Page 21

Advertising
background image

Questions? Call (315) 298-5121, or visit us online at www.fulton.com

SECTION 2

FTHC-IOM-2012-1001

INSTALLATION

2-15

!

WARNING

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.

To maintain a reasonable
temperature in the equipment area
and ensure safety to personnel, the
section of the chimney duct within
the building should be insulated.

Due to extremely high operating
temperatures of the thermal fl uid,
all exposed pipework should be
insulated, and exposed hot fl anges,
pump, valve, and fi ttings should be
shielded. Refer to Insulation section of
this manual for details.

TABLE 5 - RECOMMENDED GASKET LOADS FOR FLEXITALLIC SPIRAL WOUND CLASS 150#

GASKETS SAE GRADE 5 BOLTS OR EQUAL

Nominal Flange

Size (in.)

Number of Bolts

Diameter of Bolts

(in.)

Preferred Torque

Req. Per Bolt (ft-lb)

1/2

4

1/2

45

3/4

4

1/2

45

1

4

1/2

45

1 1/4

4

1/2

45

1 1/2

4

1/2

45

2 4

5/8

90

2 1/2

4

5/8

90

3 4

5/8

90

3 1/2

8

5/8

90

4

8

5/8

90

5

8

3/4

150

6

8

3/4

150

8

8

3/4

150

10

12

7/8

240

TABLE 6 - RECOMMENDED LOADS FOR FLEXITALLIC SPIRAL WOUND CLASS 300# GASKETS

SAE GRADE 5 BOLTS OR EQUAL

Nominal Flange

Size (in.)

Number of Bolts

Diameter of Bolts

(in.)

Preferred Torque

Req. Per Bolt (ft-lb)

1/2

4

1/2

45

3/4

4

5/8

90

1

4

5/8

90

1 1/4

4

5/8

90

1 1/2

4

3/4

150

2 8

5/8

90

2 1/2

8

3/4

150

3 8

3/4

150

3 1/2

8

3/4

150

4

8

3/4

150

5

8

3/4

150

6

12

3/4

150

8

12

7/8

240

10

16

1

368