Operation – Fulton Alliance (FT-HC) Horizontal Coil Thermal Fluid (hot oil) Heater User Manual

Page 54

Advertising
background image

© The Fulton Companies 2012

OPERATION

FTHC-IOM-2012-1001

SECTION 3

3-18

!

WARNING

Do not operate, or allow others
to operate, service or repair this
equipment unless you (they) fully
understand all applicable sections
of this manual and are qualifi ed to
operate/maintain the equipment.

Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.

4. Measure input or monitor last elbow pressure. Verify that these points are

in general correspondence with the test fi re sheet. Repeat step 2 until the
point position has a load value of 100%.

5. You are now at high fi re. Verify combustion is per test fi re sheet.

6. Once at high fi re, adjust the incoming gas pressure at the main gas

regulator to match the test fi re report. Adjust the gas servo motor to
change the last elbow pressure to match the test fi re report.

7. Adjust the air servo motor to adjust the emissions as needed.

8. Repeat step 2 but start at the high fi re point number. Continually decrease

the point number after combustion has been verifi ed at each point.

9. Once all the points have been verifi ed, press Escape until you are back to

the main menu.

10. You can observe the status of the burner by going to OperationalStat

>NormalOperation.

11. Turn the main ON/OFF switch to OFF. The control will now postpurge.

Verify ignition using steps from Setting Main Burner Ignition with the new
gas pressures.

12. Turn the main burner switch to OFF. The control will now post purge.

13. Under

Manual Operation > Auto/Manual/Off , change the operation

to Automatic and press Enter and confi rm Automatic is entered in the
current fi eld.

14. Press

Escape twice to get back to the main menu.

15. Under

Updating >ParamBackup, select LMV51 – AZL. This will store all

of the adjustments that have been made in the LMV base module to the
display. If the base module fails in the future, the display can be used to
download all of the parameters into a new base module.

16. The heater is now ready to run. Adjust your setpoint on the temperature

control to the desired temperature and turn the main ON/OFF switch to
ON for the burner to operate.

CHANGING SET POINT ON THE AZL

1. Hit

Escape to Select Operation than hit Enter and scroll to Heater Set

point, hit Enter to Set point W1 hit Enter and enter new set point with
Select buttons.

2. When accomplished hit Enter than Escape 3 times to Operational Stats

hit Enter to Normal Operation, hit Enter to get to the main screen.

Advertising