OPERATION

FTHC-IOM-2012-1001

SECTION 3

3-14

!

WARNING

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.

5. Set the fuel selector switch to the proper fuel. Restart unit normally

Oil to Gas

1. Turn

off all oil manual shutoff valves.

2. Detach the oil whips and remove the oil nozzle assembly.

3. Install the gas nozzle orifi ce assembly and open the gas cocks in the gas

train.

4. Reset the hi/low gas pressure switch.

5. Set the fuel selector switch to the proper fuel. Restart unit normally.

Flame Programmers

Siemens Linkageless Modulation, LMV 51

NOTE:

Refer to cut sheets for any non-Siemens programmers.

SETTING PILOT

1. Verify the main burner switch is in the OFF position.

2. Supply power to the heater. The AZL will display “system test” and then

move to the main menu.

3. Select

PWLogin, press Enter. Select AccessServ. Press Enter. (This type

of step will be shown as PWLogin > AccessServ for the remainder of this
section. Enter the service passwords using the arrow key. The password is
case sensitive. The case of a letter can be changed by pressing the other
arrow key. (For example, if you used the right arrow key to get to the
letter A, press the left arrow key to get a). After you have pressed Enter on
the last character of the password, press Enter once more to accept the
password. If you do not have the password, contact your Fulton Authorized
Representative to perform the changes. Service=NB# or OEM=AAAA (Enter
after each A).

4. Select

Params&Display. Press Enter. Select Ratio Control. Press Enter.

Select ProgramStop. Press Enter. Change the Program Stop to 44
Interv1
by using the arrow keys. Confi rm the change by pressing Enter.
This will set the burner management system to a ‘pilot hold’ setting.

5. Verify that the current value “curr” changes to 44 Interv 1.

6. The full listing of program stops are:

» 24: Air damper in the prepurge position

» 32: Traveling to the FGR position

» 36: Ignition position (before pilot ignition)

» 44: Ignition position (after pilot ignition)