4.5 Line Voltage/Current Sensor Diagnostics

Fig. 8. Main Board

The three-phase AC MAINS voltage wiring and the current sensor wiring must be

connected in the proper phase sequence. If there is a phase sequence error, the

display LCD will display a message ‘Check Sensor” in the upper right hand corner.

Additionally, LED D1, Check Sensor, will illuminate if there is a phasing error.

Verify that the AC MAINS voltage wires are all connected to the correct positions on

terminal block. Inspect the MAINS input wiring to verify each conductor is terminated

at the correct terminal block position. Using an AC voltmeter, measure the AC voltage

for each phase to neutral terminal and to the frame ground point.