1.0 PRE-INSTALLATION INFORMATION

The E-Mon D-Mon® Green Class kWh/Demand meter is a 3-element meter used to

monitor electric power usage of individual loads after the utility meter. Installation must

only be performed by qualified personnel and in accordance with these instructions

and all applicable local and national electrical codes. E-Mon or its representatives

assume no responsibility for damages or injury resulting from the improper installation

of this meter.

Meters are supplied in a UL Type 1 steel enclosure appropriate for indoor installation

where it will not be affected by the elements, such as moisture and extreme

temperatures.

Units designated by the “R” suffix on the model number have an extended

environmental operating range and are enclosed in a NEMA 4X enclosure to

accommodate outdoor environments. Verify the input voltage rating and configuration

on the meter label to ensure it is suitable for the intended electrical services. Green

Class meters labeled for 120/208V service MUST NOT be installed on service feeds of

277/480V and vice versa.

Verify the current sensors are sized suitably for the load to be monitored. Compare the

color of the arrows on the current sensors to the chart below to confirm the correct

current sensor is being used.

Sensor Arrow Color Code

Sensor Rating

Brown

100 Amp

Red

200 Amp

Yellow

400 Amp

Black

800 Amp

Blue

1600 Amp

White/Black 3200

Amp

Advertising