0 troubleshooting guide – E-Mon E20-6003200J-G-KIT User Manual

Page 34

Advertising
background image

GREEN CLASS METER

62-0415-01

34

10.0 TROUBLESHOOTING GUIDE

The Green Class kWh/Demand meter is calibrated and tested at the factory before

being packaged and shipped. If installed properly and in accordance with these

installation instructions, your Green Class meter should provide years of trouble free

service. If the meter should not function, the following guide will assist in

troubleshooting the installation.

NOTE: If you still need assistance after performing the above troubleshooting proce-

dures, do not remove the unit. Before removing the unit, contact E-Mon’s

technical support department at (800) 334-3666, our support experts will

assist you in detailed troubleshooting of the meter installation and assist you

in getting the unit operating correctly.

Problem

Procedure to follow

1. Display window is blank.

Check wiring to voltage terminals.
Check circuit breakers or fuses.
Verify that the power is turned on.
Test source for correct voltage.

2. Display shows incomplete figures or

numbers other than zeros when power is

turned on.

Press RESET button located on door

inside meter enclosure (5 sec.)

3. Display reading all zeros (00000000)

Determine if load is sufficient to update

the display.
Check RESET button to ensure there are

no wires or other objects pressing against

it when the door is closed.
Check the current sensors for installation

and polarity.
Be sure the current and voltage inputs

have the proper phase relationship.
Check wiring to voltage terminals.
Check circuit breaker or fuses.
Test source for correct voltage.

4. Display reads only a fraction of

consumption

Check the supply voltage to be sure that it

is on continuously 24 hrs/day.
Check the current sensors for installation

and polarity.
Check sensor wiring to the terminal strip

in meter (color coding B & W.)